煤炭工程 ›› 2014, Vol. 46 ›› Issue (4): 96-98.doi: 10.11799/ce201404033
• 研究探讨 • 上一篇 下一篇
束长富,邵如平,仲飞
收稿日期:
修回日期:
出版日期:
发布日期:
通讯作者:
Received:
Revised:
Online:
Published:
摘要:
本文分析了分布式发电对保护范围、灵敏度以及自动重合闸装置的影响,并提出了基于故障分量的自适应电流速断保护与BP人工神经网络相配合的方案。该方案利用故障电流序分量识别故障类型,BP人工神经网络间接找出系统等效阻抗的变化规律,实现了自适应电流速断保护的功能。最后,对一个10kV配电系统进行仿真,验证了保护方案的有效性。
关键词: 分布式发电, 配电网, 故障分量, 人工神经网络, 自适应电流保护
Abstract:
This paper illustrates the impact of distributed generation on the range of protection, sensitivity and reclosing, an adaptive instantaneous trip protection based on fault component combined with BP artificial neural network was proposed. This scheme uses the fault current sequence component to identify the fault type and BP artificial neural network to find the indirect changes of equivalent impedance system , achieving the adaptive current fast-tripping protection function .At last, simulation results on a 10 kV distribution system have verified the validity of the scheme proposed.
Key words: Distributed generation, Distributed networks, Fault component, Artifical neural network, Adaptive current protection
束长富,邵如平,仲飞. 含分布式电源的配电网继电保护方案[J]. 煤炭工程, 2014, 46(4): 96-98.
导出引用管理器 EndNote|Reference Manager|ProCite|BibTeX|RefWorks
链接本文: http://www.coale.com.cn/CN/10.11799/ce201404033
http://www.coale.com.cn/CN/Y2014/V46/I4/96
[1] 孙鸣. 分布式发电对配电网线路保护影响的分析[J]. 电网技术,2009,33(8):104-107. [2] 王志群. 分布式电接入位置和注入容量限制的研究[J]. 电力系统及其自动化学报,2005,17(1):53-58. [3] 杨伟,华梁.基于多Agent技术的电流速断保护自适应研究[J]. 继电器,2008,36(10): 5-10. [4] 宋凯,邰能灵,王红海. 工频变化量距离保护在含DG配电网中的应用分析[J]. 水电能源科学,2010,28(7):146-149. [5] 孙景钌. 含分布式电源配电网保护方案[J]. 电力系统自动化,2009,33(1):81-84. [6] 谢昊,卢继平. 重合闸在分布式发电条件下的应用分析[J]. 重庆大学学报(自然科学版),2007,30(2):30-33.