COAL ENGINEERING ›› 2014, Vol. 46 ›› Issue (4): 62-63.doi: 10.11799/ce201404022
Previous Articles Next Articles
Received:
Revised:
Online:
Published:
Abstract:
In some coal preparation plant main workshop, 1.2 million tons equipment reformation was completed,The excessive vibration behavior of beam-plates system caused by equipment reformation were tested. The disturbing frequency of vibrating equipment and response of floor vibration were obtained. According to the spot test results,the main cause of excessive vibration of floor is forced resonance, in addition, relatively small vertical stiffness of floor is a reason. The shortcoming of existing strengthening measures was analysis, and then the new vibration reduction treatment scheme was proposed.
Key words: floor vibration, spot testing, resonance, vibration reduction and strengthening
0 / / Recommend
Add to citation manager EndNote|Reference Manager|ProCite|BibTeX|RefWorks
URL: http://www.coale.com.cn/EN/10.11799/ce201404022
http://www.coale.com.cn/EN/Y2014/V46/I4/62
[1]徐建.建筑振动工程手册[M].北京:中国建筑工业出版社,2002. [2]GB50190-93多层厂房楼盖抗微振设计规范[S].北京:中国计划出版社,1994. [3]YBJ55-90机器动荷载作用下建筑物承重结构的振动计算和隔振设计规程[S].北京:冶金工业出版社,1990. [4]冯军和,张敏政,闫维明.多层选煤厂房的受振层楼板振动分析[J].地震工程与工程振动,2007,27(2):99-103 [5]王耀宏.多层工业厂房设备耦联振动的动力响应分析[J].煤炭工程,2007,9:97-99 [6]杜锐.某多层工业厂房楼板振动测试与分析[J].施工技术,2010,39(3):66-69. [7]GB/T14124-2009机械振动与冲击对建筑物振动影响的测量和评价基本方法及使用导则[S].北京:中华人民共和国国家质量监督检验检疫总局,中国国家标准化管理委员会,2009 [8]张旭红,郭昭胜,张善元.选煤厂房楼板抗振优化设计[J].太原理工大学学报,2006,37(4):386-388.