COAL ENGINEERING ›› 2013, Vol. 45 ›› Issue (s1): 68-70.doi: 10.11799/ce201308076
Previous Articles Next Articles
Received:
Revised:
Online:
Published:
Abstract:
Abstract: Taken Fangshan 35kV transformer substation accident for example, the paper analyzes firstly single-phase ground fault of non-grounded neutral system because of rainfall and the decrease of cable head dielectric strength, and further analyzes that the accident spread is closely related to the power grid operation mode, excessive capacitive current and intermittent arc grounding over-voltage. Then some measures to limit similar accidents are proposed and some suggestions are given finally.
Key words: Key words: non-grounded neutral system, single-phase ground fault, capacitive current, arc grounding over-voltage
0 / / Recommend
Add to citation manager EndNote|Reference Manager|ProCite|BibTeX|RefWorks
URL: http://www.coale.com.cn/EN/10.11799/ce201308076
http://www.coale.com.cn/EN/Y2013/V45/Is1/68
参考文献: 1.王显平.电力系统故障分析.中国电力出版社 2008(5) 2.丁柏林.张建权.张捷 6-35kV中性点不接地系统电容电流的危害和对策[R].安徽电力.2008.9.25(3). 3.姚秀丽,赵子军.间歇性弧光接地过电压危害及过电压保护装置.一重技术.2005年,第3期. 4.石正理.电弧接地过电压的危害及防治措施.安徽电力.2005年3月,第22卷第1期. 5.李润生.自动补偿消弧线圈装置在煤矿配电网中的应用.中国电力.1991(10). 6.许慧英.陈永义.系统电容电流的危害及补偿[M].华北电力技术 1996 7.王中英.中性点不直接接地系统的电容电流[R].天津电力 2001[5] 8.孙恒峰.王京萍.35KV中性点不直接接地系统分相接地电容测试.电网技术. 1991,21(9),19-22 9.郝小丽.单相接地故障对电网安全运行的威胁及故障处理.2006 (4) 10. 电力行业标准.交流电气装置的过电压保护和绝缘配合.DL/T 620-1997.中国电力出版社.1997.